Tuesday, February 17, 2009

ADT 72 / ADT 96

TYPE ADT 72 / ADT 96

ORDER CODE ADT 72:55272 / ADT 96:55296

SPECIFICATIONS The microcontroller based, digital temperature controller with 3 digits display.
1) The process temperature value can be indicated and adjusted easily on the digital display.
2) Without making any adjustment, control method changes between ON-OFF or Time Proportional automatically.
3) Input types are J type (Fe-CuNi) thermocouple and K type (NiCr-Ni).
4)Input type can be changed by pressing button for 3 seconds.
5) Relay output.
6) Output state (OUT) can be shown easily by LEDs.

USE OF DEVICE When the device is energized, at first desired temperature value and then in automatic mode process temperature is seen on the display. By adjusting the knob on the front panel, the desired temperature is chosen. By pressing the "MODE" button on the front panel, the desired temperature is seen on the display. 3 seconds after the adjustment, the process temperature is seen on the display automatically. Input type can be changed by pressing button for 3 seconds.

WORKING DEVICE By changing the desired value; device starts to control with Time Proportional method automatically. After the system is reached to the desired value, it starts to control with ON - OFF method.
In ON-OFF Control method; if the process temperature is bigger then the desired
temperature value, the control output is de-energized. If the process temperature is smaller then the desired temperature value, the control output is energized.
In Time Proportional Control method; due to proportional band which is 20°C, 10°C under and over the desired temperature value, device works as same as ON-OFF control method.In the other values device works related to the control period which is 10 seconds.
If the "Err" message is seen on the display, it means temperature sensor is disconnected or over temperature condition is occurred. When this message is seen, the control output is deenergized.

CONTROL RANGE

J Type: 0 °C ...400 °C , K Type: 0 °C ...800 °C

ACCURACY

For display ± %1 digit / For adjusting the knob ± %3 °C

SUPPLY VOLTAGE

230 Vac, ±% 20, 50 / 60 Hz

POWER CONSUMPTION

<>

ELECTRICAL LIFE 300.000 ON / OFF (Resistive Load)

OPERATING TEMPERATURE -5°C...+55°C

SET VALUE RANGE J Type: 0 °C ...400 °C , K Type: 0 °C ...800 °C

HYS VALUR RANGE 4 °C (for ON-OFF method)
PROPORTIONAL BAND 20 °C(for Time Proportional method)

CONTROL PERIOD 10s (for Time Proportional method)

SENSITIVITY 1°C

CONTROL OUTPUT Relay (Omron) (5A/250 Vac, , Resistive Load)

ELECTRICAL CONNECTION Socketed Connectors

CONNECTION Front Panel

PROTECTION CLASS Front : IP 54 , Connection : IP 20 , Class II
For More Information contact us:

Bulan Terang Electric
- Jl. Hayam Wuruk No.100 (Ps. HWI Lindeteves Lt. Dasar Blok.B 36)
Telp. 021-626 8347 Fax. 021-624 7742

- Gedung LTC GF1 Blok.C11 No. 5
Telp. 021-6220 1129, 6220 1139, 6231 7277
Fax. 021-622011 29
Jakarta Barat

No comments:

Post a Comment